XM31-915-HP
Power Supply
Alarms
Battery
Log In...
English
Español
Français
Português
Deutsch
Overview
Hardware
Power Supply
Batteries
Environmental I/O
Components
Network
Ethernet
Advanced
Interfaces
Network Services
Management
System Data
SNMP
Alarms
Utility Power
History
Power Supply Events
Power Supply Configuration
Battery Events
Standby Events
Alarm Log
d
Power Supply
Model
ALPHA/XM31-915-HP
Firmware
V2.06.0
Major Alarm
OK
Minor Alarm
OK
Operational Mode
Line
Charger Mode
Float
Tamper
Door closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
122.20
V
Current
6.54
A
Power
678
W
Frequency
60
Hz
Tap Status
Normal
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
5,012
Wh
1
Output
Voltage
86.56
V
Power
554
W
Apparent Power
610.24
VA
Frequency
60.01
Hz
Percent Load
47.00
%
Output Setting
90 V
Output Regulation
Coarse override
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
7.05
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.70
V/cell
Reduced Peak Mode
Disable
Total Standby Events
17
Time Since Last Standby Event
8d 9h:14m
Time in Last Standby Event
0d 3h:52m
Total Time in Standby
358
min
Standby Events Since Reset
7
Time in Standby Since Reset
234
min
Time Since Reset
17
day(s)
Total Run Time
17
day(s)
Transformer Run Time
17
day(s)
Total Downtime
0d 0h:00m
Oil Cap Lifespan Consumed
0.4
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
13
day(s)
Test Duration
10
min
Test Interval
30
day(s)
Test Inhibit
No
→ CSV
→ Excel
Copyright © 2017-2023 EnerSys. All Rights Reserved.
www.alpha.com
|
www.enersys.com
Close